This shows you the differences between two versions of the page.
| Both sides previous revision Previous revision Next revision | Previous revision | ||
| admin:poweroff [2022/02/08 12:59] peppe | admin:poweroff [2022/04/19 12:11] (current) peppe | ||
|---|---|---|---|
| Line 1: | Line 1: | ||
| ===== Διακοπή ρεύματος και επαναφορά ===== | ===== Διακοπή ρεύματος και επαναφορά ===== | ||
| - | Altus KVM 10.1.2.10 | + | PRINT BEFORE USE! | 
| + | Material may not be available during shutdown process. | ||
| + | |||
| + | Updated 19/ | ||
| + | \\ | ||
| + | * Altus KVM 10.1.2.10 | ||
| + | * Cisco switch port 6: trunk for recovery | ||
| + | * Backup! Transfer to safe media! | ||
| ==== Διακοπή ρεύματος ==== | ==== Διακοπή ρεύματος ==== | ||
| Line 7: | Line 14: | ||
| === Επίπεδο 1 === | === Επίπεδο 1 === | ||
| == HP DL145G2 == | == HP DL145G2 == | ||
| - | titan (old printserver), | + | - Close control units poweroff | 
| - | csforum\\ | + | - titan (old printserver), | 
| - | aeolus\\ | + |  | 
| - | glaucus\\ | + |  | 
| + |  | ||
| + | - unmount / | ||
| + | |||
| + | == Εργαστήρια == | ||
| + | * Shutdown/ | ||
| + | |||
| + | == 3D printers == | ||
| + | * Tevo Tarantula poweroff | ||
| + | * Sun Ultra20 poweroff | ||
| + | * Z-printer poweroff | ||
| + | * Z-printer storage shutdown (Long button press -> shutdown procedure) | ||
|  |  | ||
| - | == HP DL380G6 esxi2, 10.7.4.6 == | + | == HP DL380G6 esxi2, 10.7.4.6, iLO 10.1.2.102 | 
| - | titan-printserver (new printserver)\\ | + |  | 
| - | mysql-server\\ | + |  | 
| - | calliope-www (cse www)\\ | + |  | 
| - | == HP DL380G6 esxi3, 10.7.4.7 == | + | == HP DL380G6 esxi3, 10.7.4.7, iLO 10.1.2.103 | 
| - | zeus-debian\\ | + |  | 
| == HP DL380G7 esxi4, 10.7.4.125, iLO 10.1.2.104 == | == HP DL380G7 esxi4, 10.7.4.125, iLO 10.1.2.104 == | ||
| - | engineering www (jupiter) | + | * engineering www (jupiter) | 
| - | == Dell R630 #1 (UP) == | + | == Dell R630 #1 (UP), 10.1.2.40, iLO 10.1.2.110 | 
| - | examservers | + |  | 
| === Επίπεδο 2 === | === Επίπεδο 2 === | ||
| - | == Dell R630 #1 (UP) == | + | == Dell R630 #1 (UP), 10.1.2.40, iLO 10.1.2.110 | 
| - | gaia | + |  | 
| - | == HP DL380G6 esxi3, 10.7.4.7 == | + | == HP DL380G6 esxi3, 10.7.4.7, iLO 10.1.2.103 | 
| - | uranus-debian | + |  | 
| === Επίπεδο 3 === | === Επίπεδο 3 === | ||
| - | == EMC VNXe3100 == | + | == EMC VNXe3100, 10.7.4.9 | 
| - | poweroff | + | Poweroff | 
| + | |||
| + | Shut down the system | ||
| + | |||
| + | The shutdown process can take between 25 to 45 minutes to complete. | ||
| + | During this time, the connection to the system will be lost and | ||
| + | you will not have access to Unisphere or the online help. | ||
| + | |||
| + | 1. From Unisphere, select Settings > Service System. | ||
| + | 2. Enter the Service password to access the Service System page. | ||
| + | 3. Under Service Actions, select Shut Down System. | ||
| + | 4. Click Execute service action to shut down the | ||
| + |  | ||
| + | 5. In the Service Confirmation dialog box, click OK. | ||
| + | 6. Check the status of the shutdown process by looking at the | ||
| + | SP LED indicators: | ||
| + | |||
| + | On VNXe3100 and VNXe3150 systems, the shutdown process is complete | ||
| + | when only the Storage Processor Power LEDs are blinking and all | ||
| + | other Storage Processor LEDs are off. | ||
| + | |||
| + | 7. If you are relocating hardware, disconnect cables in the | ||
| + |  | ||
| + | |||
| + | Disconnect the power cables from disk-processor enclosure (DPE) | ||
| + | to power down the SPs. | ||
| + | Disconnect the power cable from the DAEs to power them down. | ||
| == HP DL145G2 == | == HP DL145G2 == | ||
| - | scylla | + | - scylla, iLO 10.1.2.45\\ | 
| - | rescue | + |  | 
| == HP DL380G7 esxi4, 10.7.4.125, iLO 10.1.2.104 == | == HP DL380G7 esxi4, 10.7.4.125, iLO 10.1.2.104 == | ||
| - | gatepc73\\ | + | - gatepc73\\ | 
| - | gatepc74\\ | + |  | 
| - | gatepc76\\ | + |  | 
| - | clonezilla SE\\ | + |  | 
| - | charybdis\\ | + |  | 
| + | |||
| + | == ESXi(s) == | ||
| + | * Shutdown 10.7.4.6 | ||
| + | * Shutdown 10.7.4.7 | ||
| + | * Shutdown 10.7.4.125 | ||
| + | * Shutdown 10.1.2.40 | ||
| + | * Shutdown 10.1.2.41 | ||
| + | |||
| + | == Power cables == | ||
| + | - Unplug all machines | ||
| + | - Turn off, unplug 2x online UPSs | ||
| + | - Turn off, unplug 1x rescue UPS (in rack) | ||
| + | - Unplug Cisco switch | ||
| + | - Unplug HP switch | ||
| + | - Unplug mgmt switch | ||
| + | - Unplug ATEN KVM | ||
| == personal machines == | == personal machines == | ||
| - | poweroff | + | * poweroff | 
| ==== Επαναφορά ρεύματος ==== | ==== Επαναφορά ρεύματος ==== | ||
| Line 57: | Line 118: | ||
| === Επίπεδο 1 === | === Επίπεδο 1 === | ||
| - | == EMC VNXe3100 == | + | == Power on == | 
| - | poweroν procedure | + | - ATEN KVM | 
| + | - Cisco switch | ||
| + | - HP switch | ||
| + | - mgmt switch | ||
| + | - 2x online UPSs | ||
| + | - 1x rescue UPS | ||
| + | |||
| + | == EMC VNXe3100, 10.7.4.9 | ||
| + | Power up the system (20+ minutes! Check www!) | ||
| + | |||
| + | To power up a system that is fully powered down: | ||
| + | 1. Reconnect the power cables to each DAE in the following exact order: | ||
| + | DAE 0 | ||
| + | DAE 1 | ||
| + | DAE 2 | ||
| + | Power up any remaining DAEs in ascending order. | ||
| + | |||
| + | The green Power Status LED powerlines.gif on each DAE turns on. | ||
| + | For more information on the LEDs, see System LED displays. | ||
| + | 2. Reconnect the power cables to each SP in exactly this order: | ||
| + | SP A | ||
| + | SP B | ||
| + | |||
| + | The green Power Status LED on each SP turns on. | ||
| == HP DL380G7 esxi4, 10.7.4.125, iLO 10.1.2.104 == | == HP DL380G7 esxi4, 10.7.4.125, iLO 10.1.2.104 == | ||
| - | gatepc73\\ | + | - gatepc73\\ | 
| - | gatepc74\\ | + |  | 
| - | gatepc76\\ | + |  | 
| - | clonezilla SE\\ | + |  | 
| == HP DL145G2 == | == HP DL145G2 == | ||
| - | titan (old printserver), | + | - titan (old printserver), | 
| - | csforum\\ | + |  | 
| - | aeolus\\ | + |  | 
| - | glaucus\\ | + |  | 
| - | scylla\\ | + |  | 
| - | rescue | + | - rescue, iLO 10.1.2.49\\ | 
| - | + | ||
| - | == HP DL380G6 esxi2, 10.7.4.6 == | + | |
| - | titan-printserver (new printserver)\\ | + | |
| - | mysql-server (NOT!)\\ | + | |
| - | + | ||
| - | == HP DL380G7 esxi4, 10.7.4.125, iLO 10.1.2.104 == | + | |
| - | engineering www (jupiter)\\ | + | |
| - | charybdis (NOT!)\\ | + | |
| === Επίπεδο 2 === | === Επίπεδο 2 === | ||
| - | == HP DL380G6 esxi3, 10.7.4.7 == | + | == HP DL380G6 esxi3, 10.7.4.7, iLO 10.1.2.103 | 
| - | uranus-debian | + |  | 
| - | + | * check students FS | |
| - | == Dell R630 #1 (UP) == | + | * check grads FS | 
| - | gaia | + | * check staff FS | 
| + | * check quotas | ||
| + | == Dell R630 #1 (UP), 10.1.2.40, iLO 10.1.2.110 == | ||
| + | * gaia | ||
| === Επίπεδο 3 === | === Επίπεδο 3 === | ||
| - | == HP DL380G6 esxi2, 10.7.4.6 == | + | == HP DL380G6 esxi2, 10.7.4.6, iLO 10.1.2.102 | 
| - | calliope-www (cse www)\\ | + |  | 
| + | - titan-printserver (new printserver)\\ | ||
| + | - mysql-server (NOT!)\\ | ||
| + | == HP DL380G6 esxi3, 10.7.4.7, iLO 10.1.2.103 == | ||
| + | * zeus-debian\\ | ||
| - | == HP DL380G6 esxi3, 10.7.4.7 == | + | == HP DL380G7 esxi4, 10.7.4.125, iLO 10.1.2.104 | 
| - | zeus-debian\\ | + | - engineering www (jupiter)\\ | 
| + |  | ||
| + | == Dell R630 #1 (UP), 10.1.2.40, iLO 10.1.2.110 == | ||
| + | * examservers (NOT!) | ||
| - | == Dell R630 #1 (UP) == | + | == scylla mounts | 
| - | examservers (NOT!) | + | * mount / | 
| + | == Εργαστήρια == | ||
| + | * Power up always on clients | ||
| + |  | ||
| + | == 3D printers == | ||
| + | * Sun Ultra20 poweron (+klipper, octoprint start) | ||
| + | * Tevo Tarantula poweron | ||
| + | * Z-printer poweron | ||
| + | * Z-printer storage poweron | ||
| + | |||
| + | == Close control units == | ||
| + | * Power on | ||
| + | |||
| + |  | ||